MCTT-10 Current Transformer Tester

Supplier: Maceys Electrical

Features

CONTACT THIS SUPPLIER TO FIND OUT MORE

  • Performs saturation and ratio tests on CTs using the voltage-comparison method.
  • Tests bushing CTs mounted inside transformers or switchgear.
  • Eliminates the need for large Primary Injection Test Systems to test CT saturation and ratio.
  • Saturation and ratio tests performed without changing test lead connections.
  • Overload and short-circuit protection.

Description

The MCTT-10 test set is a portable unit for performing saturation and ratio tests on current transformers using the voltage-comparison method. Model MCTT-10 provides a variable voltage output and precision instrumentation for testing single and multi-ratio CTs. All tests, saturation and ratio – can be performed without changing any leads.

Current transformers can be tested in their equipment configuration, such as being mounted in transformers, oil circuit breakers or switchgear. It is necessary for the equipment to be totally isolated from the electrical system prior to testing.

Saturation and ratio tests are critical to ensure proper electrical system reliability. Saturation tests are performed on CT’s to make sure that when a fault occurs the proper secondary current signals are delivered to the protective devices. If a CT does not deliver proper secondary current signals to a protective device because of core saturation, it is probable that the protection scheme will not operate correctly. A CT ratio test is performed to ensure that the secondary current signals are proportional and correct, in relation to the primary current.

Applications

Saturation Test

MCTT-10 provides a variable voltage output and digital instrumentation for measuring the excitation voltage and

excitation current, that results as the voltage applied to the CT under test is increased. As the CT under test begins to saturate, a large increase in current will be detected for a small increase in voltage.

Ratio Test

The ratio test is performed by comparing a voltage applied to the secondary winding to the resulting voltage produced on the primary winding. For example, if 1 volt per turn is applied to the secondary winding, the voltage present on the primary winding will be 1 volt. More specifically, if 120 volts were applied to the secondary of a 600/5 current transformer (120:1 ratio), 1 volt will be present on the primary winding.

Benefits

  • The MCTT-10 utilizes the voltage comparison method. This provides the user with the ability to measure the CT ratio without the heavy and large equipment needed to test a CT ratio using the current method. Many of the devices using the current-comparison method exceed 100 lbs (45 kg). The MCTT-10 is only 37 lbs (16.8 kg).
  • A RUN/HOLD switch freezes readings on instruments when switched to the HOLD position. This permits the user to freeze all the MCTT-10 meters for simultaneous readings.
  • A low range of 40 volts is provided for CTs that saturate at low voltages. A low voltage output range permits the MCTT-10 to test low saturation CT’s with the appropriate resolution.
  • The unit provides a high range of 1000 volts. This allows the MCTT-10 to test nearly all protection CT’s with high saturation knee points.
  • A zero-start interlock is incorporated in the unit. This minimizes the possibility of energizing the CT test with a sudden high voltage, while under test.