Home Trusted by 500,000+ buyers

Portable Appliance Tester - KEW 6205

Supplier: OBIAT Electronics Pty Ltd playlist_addCompare

This Portable Appliance Tester Complies to AS / NZS 3760. Protect life and property from faulty appliances with this tester.

Price Guide (Inc GST): POA

Portable Appliance Tester - KEW 6205 Features

  • Battery operated
  • PASS / FAIL result
  • Color status back light
  • 10 mA & 30 mA RCD test (Isolation transformer built in)
  • Memory function up to 999 data
  • Printer output
  • Complies to AS/NZS 3760

This instrument is suitable for performing tests as required by the following standards. AS/NZS 3760 In-service safety inspection and testing of electrical equipment.

FunctionTests of contents
Class I Test • Protective conductor resistance (Test current 200mA DC nominal)
• Insulation resistance test (250V or 500V)
• Leakage current test (100-253V/50Hz)
• Load current test (100-253V/50Hz)
Class II Test • Insulation resistance test (250V or 500V)
• Leakage current test (100-253V/50Hz)
• Load current test (100-253V/50Hz)
Extension Lead Test • Protective conductor resistance (Test current 200mA DC nominal)
• Insulation resistance test (between Line/Neutral-Earth short, Line/Neutral)
• Leakage current test (100-253V/50Hz)
• Polarity test
RCD Test • RCD test (10mA/30mA)

Mains voltage indlcation

Display range 30V-270V
Accuracy ±5V

Protective conductor resistance test

Measuring range 0.00-20.00Ω
Open circuit voltage 5V±0.4V DC
Measuring current 200mA DC(nominal value)
Accuracy ±3%rdg±5dgt

Insulation resistance test

Rated volatge 250V 500V
Measuring range 0.00-20.00MΩ
No-load voltage 250V DC +20%,-0% 500V DC +20%,-0%
Short circuit current 1.5mA DC or less
Accuracy ±2%rdg±3dgt

Load current/Leakage current test

Item Load current Leakage current
Mains voltage range 100-253V/50Hz
Measuring range 0.10-10.00A rms 0.10-20.00mA rms
Accuracy ±10%rdg±5dgt ±3%rdg±5dgt

RCD test

Rated voltage 230V -15% - +10%/50Hz
Rated current 10mA/30mA
Function × 1 × 5
Test duration 0.0ms-500.0ms 0.0ms-40.0ms
Operating time accuracy ±2ms(?40ms),±8ms(>40ms)

General

Power source LR6(AA)(1.5V) × 6
Applicable Standards IEC/EN61010-1 CAT II 300V, IEC/EN61010-2-030,
IEC/EN61010-031, EN61326-2-2, AS/NZ3760
Dimentions / Weight 261(L) × 104(W) × 57(D)mm / Approx. 930g (including batteries)
Included Accessories 7277(Mains lead),
7129A(Test lead with Alligator clip),
7161A(Flat test prod),
7276(Adaptor for Extension cord),
9193(Carrying case),
8928(Fuse[10A/250V]),
9121(Shoulder strap),
Buckle, LR6(AA) x 6, Instruction manual
Optional Accessories 8263-USB(USB cable with "KEW Report(software)"),
7275(Printer cable:Mini Din 6pin-D-sub 9pin),
7248(Test lead with Alligator clip and Flat test probe)