Trusted by 500,000+ buyers, sourcing equipment from 1000's of industrial brands
50 views or less

Powerstore 1000

Supplier: Powercorp Operations

Minimum operating phase-phase voltage 100V

Price Guide: POA

Powerstore 1000

Specifications

  • Design Life
    • 20 years
  • Nominal Supply Voltage
    • 3 ph, 380 Vac - 440 Vac
  • Supply Frequency
    • 50/60Hz
  • Max. Mains Voltage
    • 480V
  • Aux AC Supply….
    • 3 ph + N, 380 Vac – 440 Vac, 50/60Hz, 50A
  • Response time zero to nominal power
    • 5msec
  • Minimum operating phase-phase voltage
    • 100V
  • Fault ride through minimum phase-phase voltage
    • 0V
  • Max rate of frequency change
    • +/- 0.1Hz/ms
  • Output short circuit protection
    • Yes
  • Fault current available
    • Yes
  • Paralleling of units
    • Yes

Technical Data

  • Nominal kVA rating (@ 440V)
    • +/- 1,000kVA
  • Nominal kW rating (@ 440V)
    • +/- 1,000kW
  • Nominal kvar rating
    • (@ 440V)+/- 1,000kvar
  • Nominal Current rating
    • 1,300 A

Power Factor from 0 leading to 0 lagging is possible

  • Flywheel Energy Stored (@ 3600rpm)
    • 18MWsec
  • Estimated Discharge/Charge Time @ 100kW
    • 150s
  • Estimated Discharge/Charge Time @ 500kW
    • 30s
  • Estimated Discharge/Charge Time @ 1000kW
  • 15s
  • Flywheel Operating speed range.
    • 1800 rpm – 3600 rpm
  • Power losses @ min operating speed
    • 12kW
  • Power losses @ max operating speed
    • 15kW
  • Power Conversion efficiency charge or discharge
    • >90%
  • Minimum Charging Power spin-up
    • 35 kW
  • Nominal DC-link voltage
    • 700 Vdc

Dimensions and Weights

As per Standard Hi-Cube 40’ Shipping Container

  • Dimensions
    • (D x W x H) 12000 x 2480 x 3330 mm
  • Weight
    • app. 18,000 kg
  • Cooling
    • Refrigerative

Environmental

  • Operating Temperature
    • -5degC to +46degC
  • Humidity
    • 95% non condensing
  • Wind Loading
    • Category IV (3sec gust >65m/s)
  • Sound Power Level
    • Less than 75dB(A)

Optional the container can be prepared for a severe marine environment close to seaside installations.

Communication

  • Supported Protocols:
    • MODBus/TCP Slave
    • Pool Protocol (Powercorp Specific Protocol)
    • Others available on request

Interfaces:

  • Ethernet
    • Wired or Wireless
  • Telephone
    • PSTN/PABX
  • Cellular Telephone
    • GSM/GPRS, CDMA/1x
  • To Know More about Powerstore 1000 Please click here

To Know More about Powerstore 1000 Please click here

Showcase your business!

Connect with 600,000 industrial buyers annually

Learn more