Australia's #1 industrial directory for equipment & suppliers

Powerstore 500

Supplier: Powercorp Operations

The container can be prepared for a severe marine environment close to seaside installations.

CONTACT THIS SUPPLIER TO FIND OUT MORE

Powerstore 500

Specifications

  • Design Life
    • 20 years
  • Nominal Supply Voltage
    • 3 ph, 380 Vac - 440 Vac
  • Supply Frequency
    • 50/60Hz
  • Max. Mains Voltage
    • 480V
  • Aux AC Supply
    • 3 ph + N, 380 Vac – 440 Vac, 50/60Hz, 50A
  • Response time zero to nominal power
    • 5msec
  • Minimum operating phase-phase voltage
    • 100V
  • Fault ride through minimum phase-phase voltage
    • 0V
  • Max rate of frequency change
    • +/- 0.1Hz/ms
  • Output short circuit protection
    • Yes
  • Fault current available
    • Yes
  • Paralleling of units
    • Yes

Technical Data

  • Nominal kVA rating
    • (@ 415V) +/- 500kVA
  • Nominal kW rating
    • (@ 415V) +/- 500kW
  • Nominal kvar rating
    • (@ 415V) +/- 500kvar
  • Nominal Current rating
    • 720 A

Power Factor from 0 leading to 0 lagging is possible

  • Flywheel Energy Stored (@ 3600rpm)
    • 18MWsec
  • Estimated Discharge/Charge Time @ 100kW
    • 150s
  • Estimated Discharge/Charge Time @ 500kW
    • 30s
  • Flywheel Operating speed range.
    • 1800 rpm – 3600 rpm
  • Power losses @ min operating speed
    • 12kW
  • Power losses @ max operating speed
    • 15kW
  • Power Conversion efficiency charge or discharge
    •  >90%
  • Minimum Charging Power spin-up
    • 35 kW
  • Nominal DC-link voltage
    • 700 Vdc
  • Dimensions and Weights
  • Same as Standard Hi-Cube20’ Shipping Container
  • Dimensions
    • (D x W x H) 6000 x 2400 x 2900 mm
  • Weight
    • 12,520 kg
  • Cooling
    • Refrigerative

Environmental

  • Operating Temperature
    • -5degC to +46degC
  • Humidity
    • 95% non condensing
  • Wind Loading
    • Category IV (3sec gust >65m/s)
  • Sound Power Level
    • Less than 75dB(A)
  • Optional
    • The container can be prepared for a severe marineenvironment close to seaside installations.

Communication

  • Supported Protocols:
    • MODBus/TCP Slave
    • Pool Protocol (Powercorp Specific Protocol)
    • Others available on request
  • Interfaces:
    • Ethernet
      • Wired or Wireless
    • Telephone
      • PSTN/PABX
    • Cellular Telephone
      • GSM/GPRS, NextG

To Know More about Powerstore 500 Please click here

CONTACT THIS SUPPLIER TO FIND OUT MORE

Showcase your business!

Connect with 600,000 industrial buyers annually

Learn more